Commercial Electric Boilers in New Zealand: A Practical Guide to 20–480kW Electric Hot Water Heating
Commercial electric boilers are becoming an increasingly practical option for New Zealand buildings and industrial sites moving away from gas, diesel or coal-fired heating.
Unlike a combustion boiler, an electric hot water boiler uses immersion elements to transfer electrical energy directly into the system water. There is no burner, flue, combustion fan or on-site fuel supply.
However, choosing an electric boiler is not simply a matter of matching its kilowatt rating to the boiler being replaced. Electrical capacity, peak demand, water temperature, system volume, modulation, control integration and the actual heating-load profile all need to be considered.
FlowQuip supplies Simons ATOMIC commercial electric hot water heaters from 20kW to 480kW for hydronic heating, commercial HVAC, process hot water and heat-pump booster duties throughout New Zealand. They are particularly suitable for boosting heat-pump systems to higher final water temperatures where the heat pump alone cannot efficiently or reliably meet the required setpoint.
ATOMIC Commercial Electric Boiler Range
|
Series |
Heating capacity |
Connections |
Typical applications |
|
ATOMIC 400 |
20–200kW |
80mm rear connections |
Commercial HVAC, hydronic heating, process water and high-temperature heat-pump boosting |
|
ATOMIC 600 |
240–480kW |
100mm rear connections |
Larger commercial buildings, industrial process water, central heating plants and large heat-pump booster systems |
Key features include:
- Stainless steel hot water boiler construction
- Three-phase 415V electrical supply
- SCR step-less output modulation
- PLC controller with HMI touchscreen
- Native Modbus communication for BMS integration
- Low watt-density immersion elements
- Working pressure up to 700kPa, with higher-pressure options available
- Front access to electrical components and heating elements
- Rear-mounted flow and return connections
- Compact packaged construction
- Quiet operation
- No on-site combustion emissions
- Suitable for boosting heat-pump systems to high water temperatures
- Capacities from 20kW to 480kW
Where Do Electric Boilers Make Sense?
An electric boiler can be a strong option where the project requires:
- Removal of gas or other fossil-fuelled heating plant
- High-temperature water that is difficult for a heat pump to produce efficiently
- Boosting heat-pump-generated water to a higher final temperature
- Precise temperature control
- Fast response to changes in heating demand
- A compact plant-room footprint
- Quiet operation
- No flue or combustion-air system
- Straightforward BMS integration
- Supplementary or backup heat for a heat-pump system
- Process hot water with consistent outlet temperatures
- Heating plant without a burner, gas train or combustion fan
Electric boilers are especially useful as part of a hybrid design. A heat pump can provide the efficient base heating load and raise the water through the lower-temperature portion of the duty. The electric boiler can then provide peak capacity, backup heating or the final temperature lift to achieve the required high-temperature setpoint.
This arrangement avoids forcing the heat pump to perform the entire temperature lift under conditions where its heating capacity and coefficient of performance may be reduced.
Electric Boiler or Heat Pump?
Electric resistance boilers and heat pumps both use electricity, but they perform different jobs.
|
Consideration |
Electric boiler |
Heat pump |
|
Point-of-use heat conversion |
Essentially all electrical input becomes heat |
Delivers multiple units of heat for each unit of electricity under suitable conditions |
|
Maximum water temperature |
Well suited to high-temperature water and final temperature boosting |
Capacity and efficiency generally reduce as leaving-water temperature rises |
|
Initial plant cost |
Usually lower and simpler |
Generally higher |
|
Electrical demand |
High relative to delivered heat |
Lower for the same heat output |
|
Response |
Fast |
Depends on system and operating conditions |
|
Outdoor equipment |
Normally not required |
Usually required for air-source systems |
|
Defrost operation |
Not applicable |
May be required in cold or humid conditions |
|
Best role |
High-temperature boosting, peak, standby and process duties |
Efficient base-load heating at suitable water temperatures |
For many New Zealand projects, the best answer is not necessarily one technology or the other. A properly designed heat-pump and electric-boiler combination can provide efficient base-load heating while retaining the high-temperature capability, rapid response and resilience of an electric boiler.
Electric Boiler or Gas Boiler?
Replacing a gas boiler with an electric boiler removes the on-site combustion process. This can eliminate the need for:
- Gas burners
- Gas valves and gas trains
- Combustion fans
- Flues and associated penetrations
- Combustion-air provisions
- On-site gas combustion
- Burner servicing and combustion analysis
An electric boiler does not automatically guarantee lower operating costs. The result depends on electricity pricing, gas pricing, demand charges, the building load profile and the condition and efficiency of the existing boiler.
The main advantages are often electrification, simpler plant, precise control, reduced combustion-related maintenance and the ability to use New Zealand’s increasingly renewable electricity supply.
Why SCR Modulation Matters
Basic electric boilers may control their output by switching banks of elements on and off using mechanical contactors. This can create relatively large steps in heating output. It may also cause:
- Wider outlet-temperature fluctuations
- Repeated contactor operation
- Increased mechanical contactor wear
- Sudden changes in electrical demand
- Unnecessary cycling under low-load conditions
The ATOMIC uses Silicon Controlled Rectifier—or SCR—power control to vary heating output smoothly.
Instead of being limited to a small number of fixed stages, the boiler can closely match its output to the actual thermal load. This helps maintain a stable leaving-water temperature and reduces unnecessary switching of mechanical components.
Smooth modulation is particularly valuable when the ATOMIC is used downstream of a heat pump. The electric boiler can apply only the additional heat required to achieve the final high-temperature setpoint as the heat-pump leaving-water temperature and system demand change.
The PLC also manages the introduction of electrical load rather than bringing the complete boiler capacity online instantaneously.
How to Size a Commercial Electric Boiler
For a straightforward water-heating duty, the required heating capacity can be estimated from:
Heating capacity (kW) = flow rate (L/s) × 4.186 × temperature rise (°C)
Note: The 4.186 factor is the specific heat capacity of water (approximately 4.186 kJ/kg·°C); because 1 litre of water weighs approximately 1 kg, the formula uses flow in L/s.
For example, heating 2L/s of water through a 20°C temperature rise requires approximately:
2 × 4.186 × 20 = 167kW
For a heat-pump booster application, the calculation should be based on the additional temperature lift being provided by the electric boiler—not necessarily the system’s complete temperature rise.
For example, if a heat pump delivers 2L/s at 55°C and the electric boiler must boost this water to 70°C:
2 × 4.186 × 15 = 126kW
This calculation establishes the instantaneous heat-transfer requirement. Final selection should also consider:
- Building design heat loss
- Process demand
- Warm-up time
- Peak versus average load
- Existing system volume
- Required flow and return temperatures
- Heat-pump leaving-water temperature
- Required final boosted temperature
- Diversity
- Available electrical capacity
- Standby or redundancy requirements
- Heat-pump contribution
- Buffer-tank capacity
- Future expansion
Replacing an existing 300kW gas boiler does not necessarily mean that a 300kW electric boiler is required. Older combustion boilers are frequently oversized, while the building’s actual measured load may be substantially lower.
Where possible, use BMS trend data, fuel-consumption records or a current heat-loss calculation to establish the real load before selecting the replacement plant.
What Electrical Supply Is Required?
Commercial electric boilers impose a significant three-phase electrical load.
The approximate current for a balanced 415V three-phase resistive load can be estimated using:
Current (A) ≈ kW × 1,000 ÷ (√3 × 415)
Indicative full-load currents are:
|
Boiler capacity |
Approximate three-phase current at 415V |
|
20kW |
28A |
|
40kW |
56A |
|
80kW |
111A |
|
100kW |
139A |
|
200kW |
278A |
|
240kW |
334A |
|
320kW |
445A |
|
400kW |
557A |
|
480kW |
668A |
These figures are indicative only. Cable sizing, protection, discrimination, fault levels, installation conditions and compliance must be confirmed by the project electrical engineer. Before selecting an electric boiler, establish:
- Available transformer capacity
- Existing site maximum demand
- Switchboard capacity
- Cable route and length
- Required electrical protection
- Network or lines-company limitations
- Peak-demand charges
- Whether load-management controls are needed
- Whether the boiler will operate alongside other large electrical plant
High-Temperature Heat-Pump Boosting
Electric boilers are particularly suitable for boosting heat-pump systems to high final water temperatures.
The heat pump can be sized around the normal or base heating demand and operated at a water temperature where it can perform efficiently. The ATOMIC electric boiler can then provide the final temperature lift where required. Depending on the system design, it can provide:
- High-temperature boosting above the heat pump’s normal leaving-water temperature
- Peak-load assistance
- Backup during heat-pump maintenance
- Additional capacity during low outdoor temperatures
- Rapid system warm-up
- Legionella pasteurisation temperature support where applicable
- Industrial process temperatures above the heat pump’s practical operating range
- Temporary support following a plant failure
- Reliable final-temperature control as heat-pump output conditions change
For example, a heat pump may provide the bulk of the heating duty by raising water to 50–60°C. The electric boiler can then boost the water to a higher final setpoint such as 65°C, 70°C or another project-specific temperature.
This allows the heat pump to carry the efficient base load while the electric boiler handles only the higher-temperature portion of the duty.
The equipment may be arranged in series, through a buffer tank, or within a primary-secondary hydraulic circuit. The correct arrangement depends on:
- Heat-pump minimum flow requirements
- Required inlet and outlet temperatures
- Electric-boiler minimum flow
- System volume
- Buffer-tank configuration
- Pump arrangement
- Heat-pump and boiler control capabilities
- Required redundancy
- BMS sequencing philosophy
A buffer tank or low-loss header may be required to maintain suitable water volume, stabilise flow and prevent unwanted interaction between the heat pump, electric boiler and distribution circuits.
Suitable Applications
Commercial electric boilers can be used for:
- High-temperature heat-pump boosting
- Commercial hydronic heating
- Air-handling-unit heating coils
- Radiator heating systems
- Underfloor heating
- Industrial process hot water
- Food and beverage processing
- Wash-down water heating
- Commercial building electrification
- Gas-boiler replacement
- Heat-pump peak-load and backup heating
- High-temperature water loops
- Hospitals and healthcare facilities
- Schools and institutional buildings
- Hotels and accommodation facilities
- Manufacturing plants
- Temporary or supplementary heating
These ATOMIC units are hot water heaters, not electric steam boilers. Steam applications require equipment specifically designed and certified for steam generation.
Important System-Design Considerations
System water volume
A boiler operating in a very low-volume system may reach its setpoint rapidly. Sufficient system water volume or a correctly sized buffer tank helps stabilise operation and limits rapid temperature changes.
Minimum water flow
The boiler must have reliable water flow whenever its elements are energised. Pump proving, flow switches and control interlocks should form part of the overall safety strategy.
Expansion and pressure control
The system requires correctly sized expansion vessels, cold-fill pressure control, air elimination and appropriately rated safety valves.
Water quality
Poor water quality can shorten the life of immersion elements, pumps and other system components. System cleaning, flushing, filtration and suitable water treatment should be addressed during design and commissioning.
Control sequence
The required control philosophy should be agreed before installation. This includes:
- Boiler enable signal
- Leaving-water-temperature control
- Pump operation and proving
- BMS enable and alarm signals
- Heat-pump and boiler sequencing
- Final boosted-temperature control
- Duty/standby operation
- Load limiting
- Night setback
- Frost protection
- High-temperature shutdown
- Fault reset requirements
Service access
Although the ATOMIC has a compact footprint, adequate front clearance must be allowed so electrical components and immersion elements can be safely inspected and removed.
Why Specify an ATOMIC Electric Hot Water Heater?
The ATOMIC is designed specifically for packaged commercial and industrial water heating.
Its combination of stainless construction, low watt-density immersion elements, SCR modulation and industrial PLC control provides several practical advantages:
- Smooth matching of boiler output to the real heating load
- Stable leaving-water-temperature control
- Precise high-temperature boosting of heat-pump systems
- Reduced mechanical contactor switching
- Modbus connectivity for compatible BMS systems
- Clear local operation through an HMI touchscreen
- Front-access serviceability
- Compact plant-room installation
- No burner or combustion system
- Capacities covering 20kW through to 480kW
The system can also be programmed to control an external circulation pump where required.
Selecting an Electric Boiler for a New Zealand Project
To obtain a useful selection and project price, provide the following information:
- Required heating capacity in kW
- Application or process
- Design flow rate
- Entering and leaving water temperatures
- Heat-pump leaving-water temperature
- Required final boosted temperature
- Maximum operating temperature
- Normal operating pressure
- Required design pressure
- Available electrical supply
- Existing site maximum demand
- Required BMS interface
- Duty/standby requirements
- Indoor or outdoor location
- Available plant-room dimensions
- Preferred connection standard and size
- Heat-pump or other plant operating alongside the boiler
- Project location
- Required delivery date
If the required heating capacity is unknown, FlowQuip can help review the flow rate, temperature difference, existing boiler information, heat-pump capacity and operating profile before a unit is selected.
Frequently Asked Questions
Are electric boilers efficient?
At the point of use, essentially all electrical energy supplied to a resistance boiler becomes heat. This does not mean an electric boiler will always have the lowest operating cost. Electricity tariffs, maximum-demand charges and the alternative heating technology must also be considered.
Are electric boilers carbon-free?
An electric boiler has no on-site combustion emissions. Its overall emissions depend on the electricity used to supply it. New Zealand’s high proportion of renewable electricity makes electrification attractive, but “zero carbon” should not be claimed without considering the electricity source and complete project boundary.
What sizes are available?
FlowQuip’s Simons ATOMIC hot water range covers 20kW to 480kW:
- ATOMIC 400 Series: 20–200kW
- ATOMIC 600 Series: 240–480kW
What pressure can the ATOMIC operate at?
Standard units are available with working pressures up to 700kPa. Higher-pressure requirements should be confirmed during selection.
Can it communicate with a BMS?
Yes. The ATOMIC uses a PLC and HMI control platform with native Modbus communication for integration with compatible building-management systems.
Can an electric boiler boost a heat-pump system to a higher temperature?
Yes. This is one of the ATOMIC’s key applications. The heat pump can efficiently provide the base heating load at a moderate water temperature, while the electric boiler supplies the final temperature lift to reach the required high-temperature setpoint.
Can an electric boiler replace an existing gas boiler?
Yes, provided the actual heating load, required water temperature, electrical capacity, system hydraulics and control requirements are properly assessed. A like-for-like kilowatt replacement is not always the best selection.
Can it provide domestic hot water?
The boiler can be used as the heat source for an indirect domestic-hot-water system. Potable water separation, storage, temperature control and compliance requirements must be considered in the complete design.
Does an electric boiler require a buffer tank?
Not in every system. A buffer tank may be beneficial where system volume is low, loads vary rapidly, a heat pump is also installed, or hydraulic separation is required.
What maintenance is required?
Electric boilers avoid burner and combustion servicing, but they are not maintenance-free. Electrical connections, contactors, SCR components, safety devices, controls, pumps, water quality and immersion elements should be checked as part of planned maintenance.
Talk to FlowQuip About Your Electric Boiler Project
FlowQuip supplies commercial ATOMIC electric hot water heaters throughout New Zealand for HVAC, hydronic heating, process water, electrification and high-temperature heat-pump booster projects. We can assist with:
- Initial capacity selection
- Flow and temperature review
- High-temperature heat-pump boosting
- Electric boiler and heat-pump integration
- Buffer-tank selection
- Expansion and pressure-control equipment
- Pumps, valves and system accessories
- BMS control requirements
- Project-specific pricing and availability